White Paper | Steam Header and Near Boiler Piping Design

Fulton’s Engineered Steam Systems ensure that a steam boiler system will operate at its peak efficiency.

There are many benefits of a factory prefabricated steam system including fast tracked project management, single point design responsibility, high efficiencies, low operating costs, and more.

To ensure dry steam is delivered to the system, the steam header on Fulton pre-piped boiler steam systems includes the following:

  1. Vertical rise from the boiler
  2. Entrance to the main header is from the top
  3. Main header is sloped 1/2″ per 10′ towards drop leg
  4. Main header is sized for a maximum of 4,500ft/min at all operating conditions
  5. All steam flow is in one direction with no opposing flows
  6. Steam outlet is at the top and at the end of the header
  7. Full size, end of line, drop leg with trap connection
  8. Vacuum breaker is installed at t ahigh point on the header
  9. Pressure transducer tapping for boiler sequencing control
  10. Steam connection to boiler feedtank preheat is at a high point in the header
  11. Steam header is factory leak tested for quality assurance